General Specs | |
Model | GENNG300P-SE |
Engine Brand | Cummins |
Alternator Brand | Stamford |
Control Panel Brand | SmartGen |
Open Type Dimensions (mm) | 3800×1600×2200 mm (L*W*H) |
Open Type Net Weight (kg) | 3700 kg |
Silent Type Dimensions (mm) Silent Containerized Enclosure Dimensions |
6096×2438×2621 mm (L*W*H) |
Silent Type Net Weight (kg) | kg |
Standard Configuration (including but not limited to): High Performing Circuit Breaker, Aluminum 50° | |
Output | |
Fuel | PNG |
Rated Power | 300 kW |
Rated voltage (V) | 480/277V |
Phase | 3 phase 4 wires |
Engine/Alternator RPM (rpm) | 1800 |
Power factor | 0.8 |
Frequency (Hz) | 60Hz |
Engine | |
Engine Manufacturer | Cummins |
Engine Model | |
Ignition System | High-Energy, Multi-Cylinder Ignition System |
Speed | 1800rpm |
Number of Cylinders | 6 cylinders |
Cylinder Arrangement | Inline |
Aspiration Type | Intercooler Supercharged |
Cooling Method | Liquid-Cooled |
Compression Ratio | 11:01 |
Bore x Stroke (mm x mm) | 159mm x 159mm |
Displacement | 37.7 L |
Natural Gas Consumption Rate | 225 g/kW.h |
Oil Consumption Rate | Less than 0.24L/h |
Lubricant Grade | 20W50-C14 |
Alternator | |
Alternator Manufacturer | Stamford |
Excitation Method | Brushless, Self-excited |
Power | 300kW |
Phase | 3 phase 4 wires |
Connection Method | SAE Standard |
Insulation Grade | H |
Voltage Adjust Range | ≥5% |
Exhaust System | |
Exhaust temperature (℃) | ≥ 550℃ |
Maximum allowable exhaust back pressure | 10 kPa |
Exhaust temperature - after vortex | 580±25℃ |
Air Intake System (Maximum intake air resistance) | |
Dirty Air Filter Element | 6.2 mmH20 |
Standard Clean Air Filter Element | 3.7 mmH20 |
Heavy Duty Clean Air Filter Element | 53 mmH20 |
Cooling System | |
Exhaust Pipe | Water Jacket cooling system |
Supercharger | Liquid Cooled Supercharger |
Total Coolant Capacity | 160 L |
Thermostat Temperature Adjustment Range | 76℃ - 82℃ |
Maximum outlet water temperature (standby rated) | 104℃ - 110℃ |
Minimum Intake / Exhaust Area (m2) | 5.5m2 |
Lubrication System | |
Oil Pressure Alarm value (kPa) | 69-345kPa |
Maximum allowable oil temperature | 127℃ |
Lubricant capacity | 80 L |
Lubricant Grade | 20W50-C14 |
Ignition System | |
Ignition System | High-Energy, Multi-Cylinder Ignition System |
Ignition Firing Order | 1R-6L-5R-2L-3R-4L-6R- 1L-2R-5L-4R-3L |
Electrical System | |
Starter Motor | DC24V, Heavy-duty, Positive Gearing |
Battery Charging System | Negative Ground, 40A |
Minimum Battery Starting Capacity (Ah) | 4×165Ah |
Consumption Rate | |
Natural Gas Consumption Rate @ 100% Load LCV (low calorific value) is 35.22 MJ/m³ |
225 g/KW.h |
Oil Consumption Rate | Less than 0.24 L/h |
Intake Pipe (interface size) | DN50mm |
Control Panel | |
Brand | SmartGen |
Display | LCD |
Display Parameters The control module gives digital readouts of the following, but not limited to: |
● Generator voltage ● Output frequency ● Engine speed ● Battery voltage ● Engine hours run ● Charger voltage ● Oil pressure ● Temperature ● Fault information |
The control module has indicators for failure information: | ● Overspeed/underspeed ● Over/under voltage ● Emergency stop ● Low oil pressure ● High water temperature ● Failure to start ● Battery charger failure |
Automatic shutdown occurs under: | ● Low engine oil pressure ● High engine water temperature ● Overspeed/underspeed ● Failure to start after three attempts |